Reduces size, fan power, weight and cost of aircooled oil cooler
  

Plant Gas Compression
Service Gas Turbine Driven Compressor
Exchanger Air cooled Lube Oil Cooler
Application To cool: 15.5 litres/sec of turbine lube oil from 85°C to 71°C in a design air temperature of 37.5°C. Heat load = 373kw.

  

Design Comparison Plain Bore Finned Tube HiTRAN® System
Number of tubes/row 46 30
Number of rows of tubes 6 3
Tube length (mm) 7925 3350
Number of tube passes 6 1
Flow length (m) 47.55 3.35
Reynolds number 1344 687
Heat transfer rate (W/m2K) Finned tube 3.29 20.95
Air rate (m/s) 2.29 3.2
Air temperature rise (°C) 6.67 15.33
Number and size of fans (mm) 2 x 2250 2 x 1250
Appropriate total fan power (kW) 11.8 5.0
Plot dimensions (m) 2.74 x 8.54 2.05 x 3.96
Plot area (m2) 23.40 8.12
Finned surface (m2) 3058.3 563.2
Oil pressure drop (kPa) 71 71
Weight (kg) 8500 2200

  

Benefits
  • Requires only 1/3 of the plot area.
  • Uses less than ½ of the fan power.
  • Achieves the same duty at the same pressure drop.
  • Allows flexibility to design within noise level limits.
  • Lowest cost option

   

Best cost option engineering