Reduces size, weight and cost of shell & tube exchanger
  

Plant

Oil refinery

Service

Catalytic Cracking Plant

Exchanger

Heavy Cycle Gas Oil (HCGO) Cooler

Application

To cool: 11.76kg/sec of HCGO from 138°C to 66°C using 40.8kg/s water with inlet temperature 46°C.

Plain Tube

HiTRAN® Enhanced

Design Comparison Plain Tube HiTRAN® Enhanced
TEMA designation BEM BEM
Shell diameter (mm) 1524 689
Number of tubes 1828 371
Number of tube passes 8 1
Tube length (mm) 6096 6096
Length of flow path (m) 48.8 6.1
Tube diameter (mm) 25.4 25.4
Effective surface area (m2) 874 178.5
Performance Details
Prandtl number (in/out) 170 / 3800 170 / 3800
Reynolds number (in/out) 306 / 14 190 / 8
Overall service coefficient (W/m2K) 40 182
Tubeside coefficient (W/m2K) 51 295
Tubeside pressure drop (kPa) 70 70

  

Benefits
  • Requires less than ¼ of the effective heat transfer area.
  • Achieves the same duty at the same pressure drop.
  • Fluid residue time at the wall is reduced.
  • Risk of thermal degradation fouling is lowered.
  • Lowest cost option.

   

Best cost option engineering